INFY INFY
BEG1K0100G

30kW 1000V Bidirectional ACDC Power Module

BEG1K075G, BEG1K0100G.png
INFY

Product Introduction

BEG1K075G and BEG1K0100G are the bidirectional ACDC power modules used to connect the battery or DC bus to the AC grid.  It is specially designed for such bidirectional applications as V2G/VPF function EV chargers, retired battery utilization and the  micro grid. It also can replace traditional PCS for energy storage systems. By employing the high frequency MOSFET/SiC switch  technology, it can achieve excellent performance, high power density, high expansion ability and high reliability.

Application

  • V2G application
    INFY
    BEG1K075G_01.svg
  • BES application
    INFY
    BEG1K075G_02.svg
  • E-LOAD application
    INFY
    BEG1K075G_03.svg

Product Values

Technical Specification

  • BEG1K0100G
  • Environmental
    INFY
      Ambient temperature/storage temperature-40°C~+70°C, derating from  55°C/-40°C~+70°C
      Humidity/altitude≤95%RH, non-condensing/2000m
  • AC to DC mode-AC input
    INFY
      Rated input voltage & current range208V/380V/400V/480V, 3L+PE;
      29A/46A/44A/37A
      Input voltage/frequency range156~530Vac, 45 Hz~65 Hz
      Power factor≥0.99 full-load output power of @50%~100%
      THD≤5% full-load output power of @50%~100%
  • AC to DC mode-DC output
    INFY
      Rated power30kW
      Voltage and current range150Vdc~1000Vdc, 0~100A
      Voltage stabilization accuracy<±0.5%
      Current stabilization accuracy≤±1% (output power in 20%~100%
      Peak efficiency>97%
      Full load efficiency>96.5%
  • AC2DC and DC2AC mode conversion time (battery test)
    INFY
      10ms
  • DC to AC mode-DC input
    INFY
      DC input voltage and output powerFrom 1000 to 300Vdc, ouput power is full power 22kW/30kW
      From 300 to 150Vdc, output power is linear derating to half 11kW/15kW
      Max input current100A
  • DC to AC mode-AC output
    INFY
      Output AC voltage and output power 530~360Vac, 30kW
      360~260Vac, linear derating to 20.4kW
      260~156Vac, linear derating to 10.5kW
      Rated power 30kVA
      Output AC frequency 50Hz/60Hz
      THDi <5%
      Output power factor User setting scale, 0.8~1, -0.8~-1
      Peak efficiency >97%
      Full load efficiency >96.5%
      Off grid 1/2/3P+N+PE-Voltage  accuracy and distortion 1% and <3%
      Off grid 1/2/3P+N+PE-Power (3  phase/2 phase/single phase) 27kVA/12kVA/6kVA (R load)
      Off grid 1/2/3P+N+PE-Power  factor >0.7
      Off grid 1/2/3P+N+PE-Dynamic  voltage stability and recovery time 5% and 20ms
  • Control
    INFY
      CommunicationCAN2.0
      Indication lightGreen LED: ON for AC2DC mode, breathing for DC2AC mode; yellow LED: alarm; red LED: failure
  • Alarm and protection
    INFY
      Input overvoltage/undervoltage protectionAutomatic shutdown, automatic restart when voltage returns to normal
      Output overvoltage protectionAutomatic shutdown and lock
      Over current and short circuit  protectionAutomatic shutdown and lock, power off to start and unlock
      Over temperature protectionAutomatic shutdown, automatic restart when the temp returns to normal
  • EMC/EMI
    INFY
      TUV CE certificationIEC61000-6-1/2/3/4, Class B
  • Safety
    INFY
      UL/TUV CE/cTUVus certificationIEC62477
  • Grid connection
    INFY
      VDE-AR-N 4105, UL1741SB: 2021, CSA C22.3 No. 9, EN50549-1/-2
  • Mechanical
    INFY
      Dimensions/weight84mm (H) × 300mm (W) × 395mm (D), ≤17 kg
  • BEG1K0100G
    INFY
      The power module can not be connected to the neutral line from the grid side in on-grid mode. In off-grid mode, the module will output the neutral line to load. But in the system inner, the power module's neutral line need to be connected together.