Product Introduction
BEG1K075G and BEG1K0100G are the bidirectional ACDC power modules used to connect the battery or DC bus to the AC grid. It is specially designed for such bidirectional applications as V2G/VPF function EV chargers, retired battery utilization and the micro grid. It also can replace traditional PCS for energy storage systems. By employing the high frequency MOSFET/SiC switch technology, it can achieve excellent performance, high power density, high expansion ability and high reliability.
-
Fully isolated bidirectional ACDC, V2G support, off-grid support, max 32 modules on-grid in parallel and 16 modules off-grid in parallel
-
Constant power output@300V-1000Vdc, full power output@320V-530Vac, 200V low voltage grid support
-
Rapid current direction change within 10ms, automatic constant bus voltage support
-
Standard, de-noise and silent mode can be set
-
BABA support
-
Super compatible: compatible in size and interface with the DCDC, BiDi ACDC, BiDi DCDC, VPF power module and MCS power module
-
Conformal coating and glue flling provide high protection for high reliability
-
Peak efficiency > 97%, full load efficiency > 96.5%
-
UL/TUV CE/cTUVus, global grid code certification
-
Full SiC
Application
-
V2G application
-
BES application
-
E-LOAD application
Product Values
-
DC2AC Mode AC Output Power and DC Input Voltage Curve
-
DC2AC Mode AC Output Power and AC Output Voltage Curve
-
AC2DC Mode DC Output Power and AC Input Voltage Curve
-
AC2DC Mode DC Output Voltage and DC Output Current Curve
Technical Specification
-
BEG1K075G
-
Environmental
Ambient temperature/storage temperature -40°C~+70°C, derating from 55°C/-40°C~+70°C Humidity/altitude ≤95%RH, non-condensing/2000m -
AC to DC mode-AC input
Rated input voltage & current range 380V/400V/480V, 3L+PE;
34A/33A/27AInput voltage/frequency range 260~530Vac, 45Hz~65Hz Power factor ≥0.99 full-load output power of @50%~100% THD ≤5% full-load output power of @50%~100% -
AC to DC mode-DC output
Rated power 22kW Voltage and current range 150Vdc~1000Vdc, 0~73.3A Voltage stabilization accuracy <±0.5% Current stabilization accuracy ≤±1% (output power in 20%~100%) Peak efficiency >97% Full load efficiency >96.5% -
AC2DC and DC2AC mode conversion time (battery test)
10ms -
DC to AC mode-DC input
DC input voltage and output power From 1000 to 300Vdc, ouput power is full power 22kW/30kW
From 300 to 150Vdc, output power is linear derating to half 11kW/15kWMax input current 73.3A -
DC to AC mode-AC output
Output AC voltage and output power 530~320Vac, 22kW
320~260Vac, linear derating to 11kWRated power 22kVA Output AC frequency 50Hz/60Hz THDi <5% Output power factor User setting scale, 0.8~1, -0.8~-1 Peak efficiency >97% Full load efficiency >96.5% Off grid 1/2/3P+N+PE-Voltage accuracy and distortion 1% and <3% Off grid 1/2/3P+N+PE-Power (3 phase/2 phase/single phase) 22kVA/13.2kVA/6.6kVA (R load) Off grid 1/2/3P+N+PE-Power factor >0.7 Off grid 1/2/3P+N+PE-Dynamic voltage stability and recovery time 5% and 20ms -
Control
Communication CAN2.0 Indication light Green LED: ON for AC2DC mode, breathing for DC2AC mode; yellow LED: alarm; red LED: failure -
Alarm and protection
Input overvoltage/undervoltage protection Automatic shutdown, automatic restart when voltage returns to normal Output overvoltage protection Automatic shutdown and lock Over current and short circuit protection Automatic shutdown and lock, power off to start and unlock Over temperature protection Automatic shutdown, automatic restart when the temp returns to normal -
EMC/EMI
TUV CE certification IEC61000-6-1/2/3/4, Class B -
Safety
UL/TUV CE/cTUVus certification UL2202, CSA C22.2 No.107.1, UL9741, UL1741, UL508, IEC62909-1/2, EN62477, IEC61000 -
Grid connection
VDE-AR-N 4105, UL1741SB: 2021, CSA C22.3 No. 9, EN50549-1/-2 -
Mechanical
Dimensions/weight 84mm (H) × 300mm (W) × 395mm (D), ≤17 kg -
BEG1K075G