Product Introduction
BEG1K0110G/1K086U is the bidirectional ACDC power module used to connect the battery or DC bus to the AC grid. It is specially designed for bidirectional applications in battery energy storage systems with multiple battery groups in parallel to achieve safety isolation and fexible capacity expansion. It can also be used in retired battery utilization and AC micro grid applications. By employing the high frequency SiC MOSFET switch technology, it can achieve excellent performance, high power density, high efficiency and high reliability.
-
Non-isolated bidirectional, of-grid support, supports max 16 modules on-grid in parallel and 8 modules of-grid in parallel
-
Supports 380V/400V/480V grid, TUV CE/cTUVus, global grid code certification
-
Peak efficiency is 98.7%
-
Conformal coating and glue flling provide high protection for high reliability
-
UHPD 2.1 times of the industry's average
Application
-
BES application
-
BES application
Product Values
-
Power Module DC Voltage and Current Curve
-
Power Module AC Power and Battery Voltage Curve
-
Power Module AC Power and AC Voltage Curve
Technical Specification
-
BEG1K0110G
-
Environmental
Ambient temperature -40°C~+75°C, derating from 55°C Storage temperature -40°C~+75°C Humidity ≤95%RH, non-condensing Altitude 2000m -
On-grid mode-AC side
Rated voltage, power and current 380V/400V/62.5kVA/95A, 3L+PE Frequency 45Hz~65Hz Voltage range 260~437Vac Power factor ≥0.99 rated AC, @50%~100% power, ≥0.97 @20%~50% power Power factor correction -1~+1 adjustable THDi ≤3%, rated AC @50%~100% power -
On-grid mode-DC side
Voltage and power 650Vdc ~ 1000Vdc Max current 110A Voltage stabilization accuracy <±1% Current stabilization accuracy ≤±2%, @20%~100% power Peak efficiency ≥98.7%, rated AC&DC @50%~100% power Full load efficiency ≥98.25% -
AC2DC and DC2AC mode conversion time (battery test)
10ms -
Grid connection function
SVG, VSG, grid island, zero voltage crossing function, grid countercurrent protection -
Off-grid mode-DC input
DC input voltage 650Vdc ~ 1000Vdc@380Vac/400Vac Max Input current 110A -
Off-grid mode-AC output
Output AC voltage and output power 3L+(N)+PE, 380Vac/400Vac/62.5kW Rated power and current 62.5kVA/95A Output AC frequency 50Hz/60Hz THDi <3% Peak efficiency ≥98.7%, @30%~100% power Full load efficiency ≥98.25% AC voltage accuracy and distortion Max 1% and<3% Power factor >0.8 Dynamic voltage stability and recovery time 5% and 20ms -
Control
Communicatio CAN2.0 Indication light Green LED: ON for AC2DC mode, breathing for DC2AC mode; yellow LED: alarm; red LED: failure -
Alarm and protection
Input/output over/under voltage protection Automatic shutdown, automatic restart when voltage returns to normal Over current and short circuit protection Automatic shutdown and lock, power off to start and unlock Over temperature protection Automatic shutdown, automatic restart when the temp returns to normal -
Reliability
MTBF >300,000h -
EMC
TUV CE certification, EN61000-6-2/-4 -
Safety
TUV CE/cTUVus certification, EN62477-1:2012/A12:2021; UL1741 -
Grid connection
VDE-AR-N 4105, UL 1741SB: 2021, IEEE 1547: 2018, IEEE 1547.1: 2020, EN50549-1 -
Mechanical
Dimensions/weight 110mm (H) × 385mm (W) × 395mm (D), ≤23.6kg -
Ordering information
Type TUV CE version: BEG1K0110G -
BEG1K0110G
*DC side voltage needs t*DC side voltage needs to be higher than the AC peak line voltage + 30V.
For example, the actual AC line voltage is 528V, the module is running in on/off-grid mode, the DC side voltage must be higher than 528*1.414 + 30V = 776.6V.
*The power module can not be connected to the neutral line from the grid side.
In off-grid mode, BEG1K0110G will output the neutral line to load, but the BEG1K086U doesn't support it.
But in the system inner, the power module's neutral line need to be connected together.o be higher than the AC peak line voltage + 30V.