INFY INFY
LBG1K0120G

35kW 1000V Liquid Cooled Bidirectional ACDC Power Module

LBG1K0120G.png
INFY

Product Introduction

LBG1K0120G is the bidirectional ACDC power module used to connect the battery or DC bus to the AC grid. It specifcally aims  for bidirectional applications in V2G/VPF function EV chargers, retired battery utilization and the micro grid. It can also replace traditional PCS for energy storage systems. With the high frequency MOSFET/SiC switch technology, it can achieve excellent  performance, high power density, high expansion ability and high reliability. By employing liquid cooled design, it features high protection and zero noise.

Application

  • Application01
    INFY
    Application_BES application.svg
  • Application02
    INFY
    Application_E-LOAD application.svg
  • Application03
    INFY
    Application_V2G application.svg

Product Values

Technical Specification

  • LBG1K0120G
  • Environmental
    INFY
    • Ambient temperature/storage temperature

      -40°C~+75°C/-40°C~+75°C

    • Humidity/altitude

      ≤95%RH/2000m

  • AC to DC mode-AC input
    INFY
    • Input voltage & current range

      400/480Vac, 3L+PE; max 68A@320VAC

    • Input voltage/frequency range

      260 Vac~530 Vac, 45 Hz~65 Hz

    • Power factor

      ≥0.99  ≥ Half-load output power @ rated AC input

    • THD

      ≤5%  ≥ Half-load output power @ rated AC input

  • AC to DC mode-DC output
    INFY
    • Rated power

      35kW

    • Voltage and current range

      150Vdc~1000Vdc, 0~117A

    • Peak efficiency

      ≥97%

    • Full load efficiency

      ≥96%

  • AC2DC and DC2AC mode conversion time (with battery test)
    INFY
    • 10ms

  • DC to AC mode-DC input
    INFY
    • DC input voltage range

      On grid: 150 to 1000Vdc, of grid: 200 to 1000Vdc

    • Max input current

      133A

  • DC to AC mode-AC output
    INFY
    • Rated power

      35kVA/35kW, 3L+PE, 50Hz/60Hz

    • Output current harmonic content

      <5%

    • Unbalance of three-phase current

      2% @steady state, 4%@transient state

    • Output power factor

      User seting scale, 0.8~1, -0.8~-1

    • Low voltage ride through support, anti-islanding support

    • Peak efficiency

      ≥97%

    • Full load efficiency

      ≥96%

    • Off grid-Voltage seting

      380Vac/400Vac/480Vac (must without N wire at 480Vac)

    • Off grid-Power

      35kVA/31.5kW

    • Output voltage harmonic content

      <2% @ full R load/<5% @ full RCD load

    • Dynamic voltage stability

      5% @ 20%~100%~20% R Load

  • Control
    INFY
    • Communication

      CAN bus

    • Indication light

      Green LED: ON for AC2DC mode, breathing for DC2AC mode; yellow LED: alarm; red LED: failure

  • Power module in parallel
    INFY
    • Max number: on grid: 32, of grid: 15

  • Cooling requirement
    INFY
    • Coolant type

      G65 antifreezing liquid (60% Ethylene Glycol + 40% pure H2O)

    • Coolant temperature range

      -20°C~+60°C with full load, power derating above 60°C

    • Coolant fow requirement

      6L~10L/min,Min 0.22 bar pressure difference between the input and output liquid interface

    • Coolant pressure/volume

      Max 120PSI 8 bar, 0.25L in the module

  • Protection
    INFY
    • IP30 with condensation water protection design

  • EMC
    INFY
    • TUV CE certification

      EN61000-6-1/-2/-3/-4 Class B

  • Safety
    INFY
    • cTUVus/TUV CE certification

      UL2202, CSA C22.2 No. 107.1, UL9741, UL1741, IEC62909, EN62477

  • Grid connection
    INFY
    • Multi-country grid conformity

      VDE-AR-N 4105, EN50549-1: 2019, EN50549-10: 2022, UL 1741SB: 2021, IEEE 1547: 2018, IEEE 1547.1: 2020

  • Mechanical
    INFY
    • Dimensions/weight: 123mm (H) × 300mm (W) × 453mm (D) (excluding the holder and interface plug), ≤ 32kg