Product Introduction
S380380C-1 is a control module designed in response to the requirements of PCS system. Its main functions include: system status detection, logic control and protection; responding to the BMS to achieve rapid control and protection; responding to the EMS to achieve power dispatch; linking the communication between the monitoring system and the power module; on-grid/off-grid mode switching control; current distribution control in parallel; and rapid response to power grid mutations. ICU250K380-S/ICU500K380-S power module can realize 10ms on-grid/off-grid switching. In on-grid mode, the N line of the power module is disconnected from the N line of the grid; in off-grid mode, the N line of the power module is connected to the N line of the grid. It is featured with high reliability and miniaturized design, and suitable for on-grid and off-grid energy storage systems.
-
Miniaturized structural design, suitable for narrow installation space of the electrical cabinet, convenient for product maintenance
-
Modular design, suitable for fexible energy storage system building
-
Fast detection speed, strong anti-interference ability, strong signal processing ability
-
High integration and high reliability
Technical Specification
-
S380380C-1
-
Environmental
Working temperature
-40°C~+75°C
Storage temperature
-40°C~+70°C
Relative humidity
≤95%RH, non-condensing
Cooling method
Natural cooling
Protection class
IP20
Altitude
≤3000m
Atmospheric pressure
67kPa~106kPa
-
Power requirements
Voltage range
12V±10%
Power
≥48W
-
Communication
CAN1
Communication bus for monitoring
CAN2
In-cabinet parallel communication
CAN3
BMS communication bus
CAN4
Out-cabinet parallel communication
RS485
-
Indicator light
Green
On
On-grid operation stateGreen
On for 2s, off for 1s
Off-grid operation stateGreen
Flashing for 0.5s
Power-on state, standby, fault, shutdown, upgrade state, etc. (i.e. abnormal operation state)Green
Off
No powerRed
On
N/ARed
Flashing for 0.5s
Fan faultYellow
On
N/AYellow
Flashing for 0.5s
SPI communication fault
-
Alarm and protection
Input voltage protection
Over/under voltage protection, automatic shutdown and restart, when the voltage returns to normal
Short circuit protection
Automatic shutdown
EPO+
Emergency stop signal terminal
Normally closed, passive dry contact input signal, to the common ground GNDEPO-
Emergency stop signal terminal
Voltage ≤ 6V
-
Dimensions
270mm (width) × 125mm (depth) × 65mm (height)
-
Weight
<2kg